Crack CR-006

← Back to findings

Read-only view — engineering review is limited to CAIC engineers and administrators.

AI detection evidence

Original capture of crack CR-006
Original capture — Thermal
AI annotated detection for crack CR-006Thermal anomaly 68%
AI annotation — bounding box and confidence

Thermal anomaly consistent with trapped moisture under the coating after rainfall.

Ultralytics YOLO re-analysis

AI inference is limited to engineers and administrators.

Engineering review workflow

Your role cannot confirm, reject or action findings — the decision stays with CAIC engineering.

Reviewing engineer

Eng. Lim Sreyneang

Recommendation

Schedule repair within the current maintenance cycle and monitor after rainfall.

Finding record

Crack ID
CR-006
Zone
Z-A2 — Terminal Roof A2
Width
0 mm
Length
2.5 m
AI confidence
68%
Detected
2026-07-19
Method
Thermal
Severity
Medium
Status
AI Suspected
View zone on roof map →

Linked maintenance

No maintenance task created yet for this finding.

Example of a sealed roof crack after repair

Example after-repair evidence photo.

AI analysis history for this finding

No Ultralytics YOLO runs recorded yet — every analysis is logged here automatically.